-
您的位置:
- 網(wǎng)站首頁(yè)
- > 新聞動(dòng)態(tài)
- > 行業(yè)資訊
您的位置:
DSH 525
Subject: Applied force for internal parts
Question:
In clause 13.2, it is specified that 2N for internal parts and 30N for the outside are applied simultaneously while taking measurement of clearance. However, it is not specified that forces are applied to internal parts while taking measurements between two internal parts, ex. primary circuit component and secondary circuit component.
Which is the appropriate method to measure clearance between two internal parts ?
a) 2N forces are applied to the both parts simultaneously.
b) First, a 2N force is applied to one part and removed. And then a 2N is applied to the other one.
c) Other opinion
Decision:
First, a 2N force is applied to one part and removed. Then a 2N force is applied to the other part.
問(wèn)題:
13.2條款規(guī)定在測(cè)量間隙時(shí),內(nèi)部零部件施加2N同時(shí)外殼施加30N。然而在測(cè)量?jī)蓚€(gè)內(nèi)部零部件(例如一次電路部件和二次電路部件)時(shí),沒(méi)有規(guī)定對(duì)內(nèi)部零部件施加的力。
測(cè)量?jī)蓚€(gè)內(nèi)部零部件間隙的合適方法是什么?
a)兩部分同時(shí)施加2N的力。
b)先在一個(gè)部件上施加2N的力后移開(kāi),然后另一個(gè)部件上再加2N力。
c)其他意見(jiàn)。
決定:
先在一個(gè)部件上施加2N的力后移開(kāi),然后另一個(gè)部件上再加2N力。
************************************
DSH 541
Subject: Transformer overload
Question:
The standard does not specify a transformer overload test, as there is, , for example, in IEC 60950.
If it is obvious, based on engineering judgment of the technical design of the product, that due to a single fault condition (e.g. component failures, short circuit of functional insulation) an overload situation on a transformer is likely to occur, which approach should be followed?
1) The actual overload on the transformer shall be performed, taking into account the 'characteristics' of eventual protective devices.
2) All possible single fault conditions shall be performed. For those situations where the protective device reacts, the current through the protector shall be measured and the characteristic of the protector shall be taken into account.
3) No overload condition shall be created, since the standard does not specify this in wording.
4) Other possibilities.
Decision:
Following the standard option 2 from above has to be used.
問(wèn)題:
標(biāo)準(zhǔn)沒(méi)有與IEC 60950-1類似規(guī)定,要求變壓器過(guò)載試驗(yàn)。
如果依據(jù)產(chǎn)品的技術(shù)設(shè)計(jì)判斷,由于單一故障情況(如元器件故障、功能絕緣短路),變壓器很可能發(fā)生過(guò)載情況,應(yīng)采取哪一種方法?
1)變壓器的實(shí)際過(guò)載應(yīng)考慮到最終保護(hù)裝置的“特性”。
2)應(yīng)執(zhí)行所有可能的單一故障條件。當(dāng)保護(hù)裝置動(dòng)作時(shí),測(cè)量通過(guò)保護(hù)裝置的電流,并考慮保護(hù)裝置的特性。
3)不應(yīng)產(chǎn)生過(guò)載條件,因?yàn)闃?biāo)準(zhǔn)沒(méi)有明文規(guī)定。
4)其他的可能性。
決定:
必須使用上面的標(biāo)準(zhǔn)選項(xiàng)2。
提示:
變壓器過(guò)載是最壞的故障情況,如果有發(fā)生這種情況的可能性,變壓器和最終使用的保護(hù)裝置的應(yīng)確保過(guò)載不會(huì)導(dǎo)致火災(zāi)或觸電危險(xiǎn)。
************************************
DSH 546
Subject: Relative humidity
Question:
Various IEC standards require that specific tests be performed in a humidity chamber. The specification of the relative humidity is in several formats. How should the tolerance on the relative humidity specification be interpreted?
Decision:
(1) Unless clearly noted otherwise, the tolerance specified for humidity is considered to be in percent relative humidity, % RH.
(2) It is intended that the set point of the humidity chamber controller be set within the specified range and that the humidity remains within the specified range.
(3) Confirmation that humidity is within the specified range shall be made by a humidity measuring instrument according to CTL DSH 251A.
問(wèn)題:
各種IEC標(biāo)準(zhǔn)要求在濕度室中進(jìn)行特定的試驗(yàn)。相對(duì)濕度的規(guī)格有幾種格式。相對(duì)濕度規(guī)格上的容差應(yīng)如何解釋?
決定:
(1)除非另有明確說(shuō)明,指定的濕度容差被認(rèn)為是百分比相對(duì)濕度,% RH。
(2)濕度室控制器的設(shè)定點(diǎn)應(yīng)設(shè)定在規(guī)定的范圍內(nèi),濕度保持在規(guī)定的范圍內(nèi)。
(3)濕度在規(guī)定范圍內(nèi),由濕度測(cè)量?jī)x根據(jù)CTL DSH 251A進(jìn)行確認(rèn)。
提示:
CTL DSH 251已經(jīng)被OD-5014替換,見(jiàn)以下鏈接
DSH 2106測(cè)量?jī)x器有效性+OD-5014儀器精度要求